Fire Testing Equipment

Fire Testing Equipment for Building Materials

Reaction-to-fire and fire-resistance equipment for Euroclass (EN 13501-1), ASTM, BS 476, NFPA and IMO classification of construction products.

Fire Testing Equipment for Building Materials

Classify cladding, insulation, boards and linings with confidence

Façade panels, insulation, gypsum and cement boards, wall linings, floor coverings, roofing and PV modules must prove their fire performance before they are approved for projects. The equipment on this page covers every test used for Euroclass classification to EN 13501-1, from non-combustibility (ISO 1182) and heat of combustion (ISO 1716) to the single burning item (EN 13823), the single-flame test (ISO 11925-2) and the flooring radiant panel (ISO 9239-1), together with the cone calorimeter, room corner test, NBS smoke chamber, oxygen index and large fire resistance furnaces for walls, doors and seals.

Building Materials: fire test equipment

Single Burning Item (SBI) Test Apparatus – FTech-EN 13823 (EN 13823, EN 13501-1)

Single Burning Item (SBI) Test Apparatus

The reference test for Euroclasses A2 to D of construction products other than floorings. A corner specimen is exposed to a sand-box propane burner under an exhaust hood, and the system calculates heat release rate (HRR), smoke production rate (SPR), FIGRA, SMOGRA, total heat and smoke, O2 consumption and CO/CO2 production, while lateral flame spread and flaming droplets are observed.

  • ModelFTech-EN 13823
  • StandardsEN 13823, EN 13501-1
  • MeasuredHRR, SPR, FIGRA, SMOGRA, THR, TSP, O2, CO, CO2
  • BurnerPropane sand-box burner, 30.7 kW
Request a quote
Cone Calorimeter – FTech-ISO 5660 (ISO 5660, ASTM E1354)

Cone Calorimeter

The most widely used bench-scale instrument for fire behaviour. Based on oxygen consumption (13.1 MJ released per kg of O2 consumed), it measures heat release rate, time to ignition, mass loss, O2 consumption, CO and CO2 production and smoke. The data acquisition software runs the whole test and also allows tests at user-defined heat flux and temperature profiles.

  • ModelFTech-ISO 5660
  • StandardsISO 5660, ASTM E1354, ASTM E1474 …
  • PrincipleOxygen consumption calorimetry
  • MeasuredHRR, ignition time, MLR, O2, CO, CO2, smoke
Full specifications
ModelFTech-ISO 5660
StandardsISO 5660, ASTM E1354, ASTM E1474, ASTM E1740, ASTM F1550, ASTM D6113, BS 476-15, NFPA 264
PrincipleOxygen consumption calorimetry
MeasuredHRR, ignition time, MLR, O2, CO, CO2, smoke
Request a quote
Fire Resistance Test Furnace (Vertical) – FTech-EN 1363-1 (EN 1363-1, ISO 834)

Fire Resistance Test Furnace (Vertical)

Large-scale furnace that rates walls, doors, fire dampers, joints and penetration seals for load-bearing capacity, integrity and insulation. Lined with 1400-grade insulating bricks and refractory castables, it follows the ISO 834 / EN 1363 standard curve, BS 476 or the IMO hydrocarbon curve up to 1250 °C. It is built and fired at the factory, then dismantled into modules for shipping and re-assembly on site.

  • ModelFTech-EN 1363-1
  • StandardsEN 1363-1, ISO 834, BS 476-20 to 24 …
  • Max. temperature1250 °C
  • CurvesISO 834 / EN 1363, BS 476, IMO hydrocarbon
Full specifications
ModelFTech-EN 1363-1
StandardsEN 1363-1, ISO 834, BS 476-20 to 24, BS EN 1364-1, BS EN 1366-8
Max. temperature1250 °C
CurvesISO 834 / EN 1363, BS 476, IMO hydrocarbon
Request a quote
Flooring Radiant Panel Test Apparatus – FTech-ISO 9239 (ISO 9239-1, ISO 9239-2)

Flooring Radiant Panel Test Apparatus

Measures the critical radiant flux of floor coverings and attic insulation, the key result for flooring classes A2fl to Dfl. Stainless-steel construction with an embedded computer, alarms and USB/RS232 ports for reports.

  • ModelFTech-ISO 9239
  • StandardsISO 9239-1, ISO 9239-2, ASTM E648 …
  • Heat flux meter0–20 kW/m², ±0.2 kW/m²
  • Propane flow0.026 ± 0.002 L/s
Full specifications
ModelFTech-ISO 9239
StandardsISO 9239-1, ISO 9239-2, ASTM E648, ASTM E970, NFPA 253
Heat flux meter0–20 kW/m², ±0.2 kW/m²
Propane flow0.026 ± 0.002 L/s
Pyrometer400–600 °C
Request a quote
Roof Coverings & PV Module Fire Test Machine – FTech-UL1730 (UL 1730, UL 790)

Roof Coverings & PV Module Fire Test Machine

Evaluates the fire resistance of roof coverings and roof-mounted photovoltaic modules and classifies specimens as Class A, B or C by flame spread (1.82 / 2.4 / 3.9 m). Electronic deck-tilt control, regulated gas and air flow and automatic data acquisition.

  • ModelFTech-UL1730
  • StandardsUL 1730, UL 790, IEC 61730-2 …
  • Air velocity19 ± 8 km/h
  • Flame temperature888 ± 28 °C
Full specifications
ModelFTech-UL1730
StandardsUL 1730, UL 790, IEC 61730-2, ASTM E108
Air velocity19 ± 8 km/h
Flame temperature888 ± 28 °C
Request a quote
Non-Combustibility Test Furnace – FTech-ISO 1182 (ISO 1182, BS 476-4)

Non-Combustibility Test Furnace

Determines whether a building product is non-combustible, a requirement for Euroclasses A1 and A2. Patented control system, Ni-Cr heating element and sheathed thermocouples; the furnace reaches thermal equilibrium in about 35 minutes and prints reports and curves directly.

  • ModelFTech-ISO 1182
  • StandardsISO 1182, BS 476-4, BS 476-11 …
  • Heating element80% Ni / 20% Cr strip, 3 mm × 0.2 m
  • Time to equilibrium≈ 35 min
Full specifications
ModelFTech-ISO 1182
StandardsISO 1182, BS 476-4, BS 476-11, ASTM E136
Heating element80% Ni / 20% Cr strip, 3 mm × 0.2 m
Time to equilibrium≈ 35 min
Request a quote
Single-Flame Source Ignitability Tester – FTech-ISO 11925-2 (EN ISO 11925-2, DIN 53438)

Single-Flame Source Ignitability Tester

Small-flame ignitability test required for Euroclasses B to E. Imported burner and gas flow valve for a precise flame, adjustable flame height with automatic ignition and all-stainless-steel internal fixtures.

  • ModelFTech-ISO 11925-2
  • StandardsEN ISO 11925-2, DIN 53438, DIN 4102-B1
Request a quote
Room Corner Test Facility – FTech-ISO 9705 (ISO 9705, ISO 13784-1)

Room Corner Test Facility

Full-scale test in which wall linings are fixed inside a standard room and ignited with a propane burner in the corner. Heat release rate and time to flashover are the main results, together with temperatures, total heat, CO and CO2.

  • ModelFTech-ISO 9705
  • StandardsISO 9705, ISO 13784-1, ASTM E1537 …
Full specifications
ModelFTech-ISO 9705
StandardsISO 9705, ISO 13784-1, ASTM E1537, ASTM E603
Request a quote
Smoke Density Tester (Building Materials) – FTech-ASTM D2843 (ASTM D2843)

Smoke Density Tester (Building Materials)

Measures the static smoke density of burning or decomposing materials from the loss of light. Enamelled corrosion-resistant cabinet, main and auxiliary burners, automatic ignition, timing and smoke extraction, with live and historical smoke curves.

  • ModelFTech-ASTM D2843
  • StandardsASTM D2843
  • Light absorption0–100 %, ±1 %
  • TimingPLC, 0.1 s
Request a quote
Bomb Calorimeter (Heat of Combustion) – FTech-ISO 1716 (ISO 1716)

Bomb Calorimeter (Heat of Combustion)

Determines the gross heat of combustion of construction materials in a constant-volume bomb, a requirement for Euroclasses A1 and A2. Automatic temperature acquisition and storage with real-time curves and fault display.

  • ModelFTech-ISO 1716
  • StandardsISO 1716
  • Bomb300 ± 50 mL, 21 MPa
  • CrucibleØ 25 mm, 14–19 mm high
Request a quote
Smoke Toxicity Test Device – FTech-DIN 53436 (DIN 53436, JIS 1321)

Smoke Toxicity Test Device

Generates thermal decomposition products under air flow with a moving furnace (DIN 53436) for toxicological evaluation, adjustable to different smoke-generation rates and concentrations and exposure durations.

  • ModelFTech-DIN 53436
  • StandardsDIN 53436, JIS 1321
Request a quote
Radiant Panel Flame Spread Apparatus – FTech-ASTM E162 (ASTM E162, ASTM D3675)

Radiant Panel Flame Spread Apparatus

One of the most widely used flame spread methods in the USA, cited by NFPA 130 for interior panels, ceilings, insulation, windows and seat parts of rail vehicles. Stainless-steel frame, electronic ignition with flame-failure safety, 8 stack thermocouples and automatic data acquisition.

  • ModelFTech-ASTM E162
  • StandardsASTM E162, ASTM D3675, NFPA 130
Request a quote
NBS Smoke Density Chamber – FTech-ISO 5659-2 (ISO 5659-1, ISO 5659-2)

NBS Smoke Density Chamber

Single-chamber optical smoke density test with a radiant cone up to 50 kW/m², used for buildings, rail (EN 45545-2) and ships (IMO). Includes a weighing system for mass loss, a water-cooled heat flux meter and LabVIEW software with calibration, verification and test modes.

  • ModelFTech-ISO 5659-2
  • StandardsISO 5659-1, ISO 5659-2, ASTM E662 …
  • Heat flux10–60 kW/m² (3000 W cone)
  • Weighing0–1000 g, ±0.01 g
Full specifications
ModelFTech-ISO 5659-2
StandardsISO 5659-1, ISO 5659-2, ASTM E662, IMO FTP Code
Heat flux10–60 kW/m² (3000 W cone)
Weighing0–1000 g, ±0.01 g
Request a quote
Lateral Spread of Flame Apparatus – FTech-ISO 5658-2 (ISO 5658-2, IMO FTP Code Res. A.653(16))

Lateral Spread of Flame Apparatus

Determines the lateral flame spread of building products and marine surface finishes, used to evaluate fire-retardant performance and IMO approval.

  • ModelFTech-ISO 5658-2
  • StandardsISO 5658-2, IMO FTP Code Res. A.653(16), ASTM E1317
Request a quote
Roof Materials External Fire Test Apparatus – FTech-ENV 1187 (ENV 1187, ISO 12468-1)

Roof Materials External Fire Test Apparatus

Tests roofs exposed to external fire using a burning wood crib with wind and radiant heat. 600 × 600 mm radiant panel, specimen holder adjustable 0–50°, VFD-controlled air duct and high-voltage ignition with automatic gas shut-off.

  • ModelFTech-ENV 1187
  • StandardsENV 1187, ISO 12468-1
Request a quote
Limiting Oxygen Index (LOI) Tester – FTech-ISO 4589-2 (ISO 4589-2, ASTM D2863)

Limiting Oxygen Index (LOI) Tester

Finds the minimum oxygen concentration that just supports combustion of plastics, laminates, foams, sheets and films. Paramagnetic oxygen sensor, mass flow controllers that set O2/N2 automatically and a PLC touch screen.

  • ModelFTech-ISO 4589-2
  • StandardsISO 4589-2, ASTM D2863
  • Range0–100 % O2
  • Accuracy±0.1 %
Request a quote
High-Temperature Oxygen Index Apparatus – FTech-ISO 4589-3 (ISO 4589-3, NES 715)

High-Temperature Oxygen Index Apparatus

Adds an electric preheater around the chimney of the LOI tester to measure the oxygen index at elevated temperature and the ignition temperature of materials at a set oxygen concentration (rail and naval specifications).

  • ModelFTech-ISO 4589-3
  • StandardsISO 4589-3, NES 715
Request a quote

More equipment in this section

EquipmentModelStandards
Difficult-Flammability Tester (Brandschacht)FTech-DIN 4102DIN 4102
Rigid Foam Vertical Combustion TesterFTech-ASTM D3014ASTM D3014
Façade Fire Test Rig for External Wall InsulationFTech-BS 8414-1BS 8414-1, BS 8414-2
Smouldering Characteristics Tester for Building MaterialsFTech-BS 8414-2BS 8414
Flame Propagation Calorimeter—ISO 12136
Hot Surface Insulation Performance Tester (Plates & Pipes)FTech-ASTM C411ASTM C411, ASTM C447, ISO 8142
PV Module Flammability ApparatusFTech-IEC61730-2FISO 11925-2, IEC 61730-2
Direct Flame Impingement TesterFTech-BS 476-12BS 476-12
Combustibility Test ApparatusFTech-AS 1530.2AS 1530.2
Early Fire Hazard Radiant Panel TesterFTech-AS 1530.3AS 1530.3

Standards & classification

EN 13501-1 reaction-to-fire classes and the equipment they require

ClassConstruction productsFlooringsEquipment
A1 / A1flEN ISO 1182 + EN ISO 1716EN ISO 1182 + EN ISO 1716Non-Combustibility Test Furnace
Bomb Calorimeter (Heat of Combustion)
A2 / A2flEN ISO 1182 or EN ISO 1716 + EN 13823EN ISO 1182 or EN ISO 1716 + EN ISO 9239-1Non-Combustibility Test Furnace
Bomb Calorimeter (Heat of Combustion)
Single Burning Item (SBI) Test Apparatus
Flooring Radiant Panel Test Apparatus
B, C, D / Bfl, Cfl, DflEN 13823 + EN ISO 11925-2EN ISO 9239-1 + EN ISO 11925-2Single Burning Item (SBI) Test Apparatus
Flooring Radiant Panel Test Apparatus
Single-Flame Source Ignitability Tester
E / EflEN ISO 11925-2EN ISO 11925-2Single-Flame Source Ignitability Tester
F / FflNo performance determinedNo performance determined—

Frequently Asked Questions

Which tests does a façade or insulation manufacturer need first?

Most manufacturers start with ISO 11925-2 and EN 13823 (SBI), which together give classes B to E, and add ISO 1182 and ISO 1716 when they target A1 or A2 non-combustible classes. The cone calorimeter is the most useful development tool alongside them.

Is the fire resistance furnace delivered as one piece?

No. It is built and fired at the factory, then dismantled into modules for transport and re-assembled and commissioned on site.

Equip your Building Materials fire testing laboratory

Share the products and standards you test to, and EnmaTech will recommend the right equipment for your laboratory in Saudi Arabia and prepare a quotation.